UL-1000KW-2132KWH
System Features
Technical Parameters
UL-1000KW-2132KWH |
System Model
UL-1000KW-2132KWH
Revisions
V1.0
Date
May 11, 2020
SYSTEM INFORMATION
Max. power
1,000kW
Nameplate Capacity
2,132kWh
Compatible Inverters1
PE: FP1700K(K2), FP1770K(2), FP1875K(K2).
SMA: SCS 2500-EV.
Sungrow: SC1200UD, SC1375UD, SC1575UD.
BATTERY INFORMATION
Battery Chemistry
LFP
Cell Make / Type
CATL / 280Ah
Configuration
340S7P
Nominal Voltage
1,088V
Voltage Range
952 ~ 1,224V
PROTECTIONS AND SAFETY DEVICES
System Level Lockable Disconnect
Yes
Rack Level Lockable Disconnect
Yes
Short Circuit Protection
Yes
Lightning Protection
Yes
Over-charge / Over-discharge Protection
Yes
Over-temperature Protection
Yes
Combustible Gas Detection
Yes
Fire Detection
Yes
Intrusion Detect System
Yes
Exhaust Fan for Gas Venting
Yes
Water System (dry pipe)
Yes
External Accessible E-stop
Yes
External Accessible Fire Control Penal
Yes
System Controller
Yes
Uninterruptible Power Supply (UPS)
Yes
WORKING CONDITIONS
Degree of Protection
NEMA 3R / IP54
Noise Emission
≤75dB @1m
Operating Temperature Range
-22°F ~ 113°F / -30°C ~ 45°C
Relative Humidity
0~95% (No condensing)
Max. Working Altitude
6,500’ / 2,000m
GENERAL INFORMATION
Dimensions (W*H*D)
20’*9.5’*8’ / 6,058*2,896*2,438mm
Weight (with & without batteries)
58,700lbs & 18,800lbs / 26.6t & 8.5t
Cooling
HVAC
Fire Suppression System
FM200 (Novec 1230 optional)
Aux. Power Supply
480VAC 60Hz 3P3L
Max. Current of Aux. Power Supply
60A
Communication Protocol
Modbus TCP/IP
Certificate & Compliance
UL1973, UL9540A, UL9540