SU502U250L | SU502E200L

System Features


Technical Parameters

UL-250KT-502KWH


  • System Model

    SU502U250L | SU502E200L

  • SYSTEM INFORMATION

     

  • Nominal AC Power

    250kW | 200kW

  • Nameplate Capacity

    502kWh

  • BATTERY INFORMATION

     

  • Battery Chemistry

    LFP

  • Capacity

    280Ah

  • Configuration

    280S2P

  • Nominal Voltage

    896V

  • Voltage Range

    784~1000V

  • INVERTER INFORMATION

     

  • Max. AC Power

    2 x 125kW | 2 x 100kW

  • Nominal Grid/Islanding Voltage

    480V | 400V

  • Grid Voltage Range

    422.4V~528V | 320~456V

  • Power Factor

    -1~1, continuously adjustable

  • Nominal Grid Frequency

    60Hz | 50Hz

  • Isolation

    Transformerless

  • WORKING CONDITIONS

     

  • Degree of Protection

    NEMA 3R / IP54

  • Noise Emission

    ≤72dB @1m

  • Operating Temperature Range

    -22°F ~ 113°F / -30°C ~ 45°C

  • Relative Humidity

    0~95% (No condensing)

  • Max. Working Altitude

    6,500’ / 2,000m 

  • SYSTEM INFORMATION

     

  • Dimensions (W*H*D)

    14.9'×8.2'×5.2’/ 4,550×2,500×1,600mm

  • Weight (with & without batteries)

    15,500lbs & 6,600lbs / 7t & 3t 

  • Cooling Method of Battery Chamber

    HVAC

  • Fire Suppression System

    FM-200 (Novec 1230 optional)

  • Cooling Method of PCS Chamber

    Forced air cooling with replaceable fan module

  • Communication Protocol

    Modbus TCP/IP

  • Certificate & Compliance

    UL1741, UL 1741SA, IEEE1547, UL1973, UL9540A, UL9540 | IEC62619, IEC61000, IEC62477, G99, AS4777.2